Inverter Output Specifications:
Continuous Output Power: 4000 Watts
Surge Rating: 12000 Watts (20 Seconds)
Output Waveform: Pure Sine/Same as input (Bypass Mode)
Output Voltage 100-110-120Vac
Nominal Efficiency: >88% (Peak)
Line Mode Efficiency: >95%
Output Frequency: 50Hz +/- 0.3Hz / 60Hz +/- 0.3Hz
Typical Transfer Time: 10ms (Max)
THD: < 10% DC
Input Specifications
Nominal Input Voltage: 24.0Vdc
Minimum Start Voltage: 20.0Vdc
Low Battery Alarm: 21.0Vdc-22.0Vdc
Low battery Trip: 20.0Vdc-21.0Vdc
High Voltage Alarm: 32.0Vdc
Low battery Voltage Restart: 31.0Vdc
Idle Consumption: 52.5 Watts
Idle Consumption with Power Saver Mode ON: 20.9 Watts
Transfer Switch Specifications
40 amp automatic transfer switch
10 ms (max)
Dimensions
Unit Weight: 62 lbs.
Unit Size L x W x H: 23.5 x 8.74 x 7.10 inches
Shipping Weight: 72 lbs.
Shipping L x W x H 30.5 x 14.25 x 13.75 inches